The circuit breaker has an outdoor compact floor-mounted tank-type structure, equipped with a CT35 spring operating mechanism. The mechanism is integrally mounted with the body, ensuring simple installation, easy commissioning, and reliable operation, making it suitable for frequent operations. The mechanism’s lifespan exceeds 10,000 operations.
It adopts a compressed air arc-extinguishing structure with strong breaking capability. It can interrupt 40 kA of fault current up to 12 times, setting a domestic record. The sealing performance is reliable, using imported sealing gaskets. The dynamic seal employs a “V”-shaped sealing ring with a spring pressure compensation structure. The secondary wiring board for the current transformer is supplied by a joint venture, ensuring an annual leakage rate of <0.5%.
The internal current transformers use microcrystalline alloy materials with high magnetic conductivity, and the accuracy class can reach 0.2 or 0.2S. Based on user requirements, up to 12 current transformers can be included. It is capable of handling no-load long lines of up to 50 km without reignition.
No. Parameter Name Unit Parameter Value 1 Rated voltage kV 40.5 2 Rated insulation level kV 185 (lightning impulse, full wave peak) /
95 (power frequency, 1 min)3 Rated current A 2000 4 Mechanical life Times 10,000 5 Rated SF6 gas pressure (20℃ gauge pressure) MPa 0.5 6 Alarm/minimum functional pressure (20℃ gauge) MPa 0.45 7 Rated short-circuit breaking current kA 40 8 Rated short-circuit making current (peak) kA 100 9 Rated short-time withstand current (thermal) kA 40 10 Rated short-time withstand current (dynamic) kA 100 11 Rated out-of-step breaking current kA 10 12 Accumulated breaking times (rated short-circuit) Times 12 13 Rated short-circuit duration s 4 14 Closing time (rated operating voltage) s ≤0.15 15 Opening time (rated operating voltage) s ≤0.06 16 Rated operating sequence – O—0.3s—CO—180s—CO* 17 Rated switching current (single capacitor bank) A 400 18 SF6 gas annual leakage rate %/Year ≤0.5 19 SF6 gas moisture content (V/V) ppm ≤150×10⁻⁶ 20 Rated operating voltage (CT14 spring mechanism) – See notes 21 Closing/Opening coil voltage V DC 110/220 22 Energy storage motor voltage V AC 220/380; DC 110/220 23 SF6 gas weight kg 8 24 Circuit breaker weight (including mechanism) kg 1400
Phone: +8613736779975
E-mail: sales@vcbbreaker.com
Address: 66 Punan Road, Yueqing Economic Development Zone, Zhejiang, China
Hakimiliki © 2025 Yangmei Kikundi cha Umeme Haki zote zimehifadhiwa
Tovuti hii hutumia vidakuzi ili kuhakikisha unapata matumizi bora kwenye tovuti yetu.